Solar Inverter Error Codes by Brand
An inverter error code means only what that manufacturer’s manual says for that model. SMA, Fronius, and every other brand use different numbers, and the same digits can mean different things on two products from one company. The codes in this article are limited to two SMA documents and two Fronius documents. If your display shows any other number, stop and use the manual for that exact model.
Grid-voltage messages on the SMA Sunny Boy series cited below mean the inverter has disconnected from the utility. Insulation messages mean the DC circuit’s resistance to ground is too low for that product’s test, and both SMA and Fronius assign the repair to a qualified person. Do not open the inverter, unplug DC connectors, or separate strings to clear a code.
For the insulation fault family, read inverter isolation faults and the qualified-service boundary. For the wider guide map, see the solar inverter topic guide.
Read the code before you touch anything
Write down the full event or state number, the words on the display, the time, and whether the inverter is still feeding the grid. Photograph the label with the model number. Those four items are what the manual and the service technician use to tell a grid trip from an insulation trip.
A number from a forum list, or from a different brand, is not evidence. SMA’s service manual for the Sunny Boy 3000TL, 3600TL, 4000TL, 5000TL, and 6000TL (document SB30-60TL-21-SG-en-11) uses three-digit grid events. SMA’s technical information “Insulation Error in PV Systems” (Isolationsfehler-TI-en-10) uses 3501 for low insulation resistance. Fronius uses state 475 in its DC insulation paper. In the GEN24, Tauro, and Verto country-setup instructions, the function text shows an isolation trip as status code 1082 and an isolation warning as status code 1083, while the parameter table in the same section shows that trip as 1182 and that warning as 1183. None of those numbers is a universal solar code.
Grid events in one SMA Sunny Boy manual
The following rows are the grid-fault text in SMA service manual SB30-60TL-21-SG-en-11. They apply to the Sunny Boy 3000TL through 6000TL covered by that manual. Another SMA family can use different event numbers.
| Event | What that manual says |
|---|---|
| 101 to 103 | Grid fault. Grid voltage or grid impedance at the inverter’s connection point is too high. The inverter has disconnected from the utility grid. |
| 202 to 203, and 205 | Grid fault. The utility grid has been disconnected, the AC cable is damaged, or the grid voltage at the connection point is too low. The inverter has disconnected. |
| 301 | Grid fault. The ten-minute average of grid voltage is outside the permitted range. Grid voltage or grid impedance at the connection point is too high. The inverter disconnects to maintain power quality. |
The manual’s corrective steps for events 202 to 203 and 205 include checking that the breaker is on and that the AC cable is undamaged and correctly connected, then comparing the grid voltage with the permitted range. If local grid conditions put the voltage outside that range, the manual says to contact the grid operator. If the voltage stays inside the range and the message remains, it says to contact SMA Service. Checking and reconnecting AC conductors is service work. A homeowner can record the event and see whether a breaker handle has tripped. Cable repairs and any change to voltage limits belong to a qualified person and the utility.
The manual does not publish one national window such as a single “216 to 264 volt” band. It says “the permissible range.” That range is the setting for the installation, not a number this article can invent.
SMA insulation events
SMA’s technical information “Insulation Error in PV Systems” says SMA inverters measure insulation resistance on the DC side before they connect to the utility grid. A low result is event 3501. The display text is “Insulation failure” and “Check generator.” The explanation in the document: the insulation resistance of the DC installation is or was too low, so the inverter disconnects or refuses to connect. The usual cause is defective insulation or a faulty plug on the modules or in the DC wiring.
The same document says event 3501 can appear for a time because of rain or dew, and that wind can push a cable with damaged insulation against a grounded part. It groups events 3501, 3502, and 3503 as insulation errors, and events 3601 and 3701 as leakage or residual-current messages. For any of those messages it recommends inspection by a qualified person. The opening of the document says the corrective measures may only be carried out by qualified persons.
Seeing 3501 after rain is a reason to call that qualified person, not a reason to unplug connectors and dry them. The document also says insulation faults are not always easy to find and that a thorough inspection is still required.
Fronius isolation codes
Fronius’s June 2026 paper “DC Insulation Resistance of PV Systems” says that if the inverter shows state 475, “LOW DC ISOLATION,” a qualified electrician must test the PV system for ground faults. That paper is the source for state 475. It is not a license for the owner to lower the trip threshold. The paper says any change to the threshold has to be clarified with the owner, the authorities, the manufacturers, and the installer.
A different Fronius document, the GEN24, Tauro, and Verto country-setup instructions (42,0426,0413,EA), describes an adjustable isolation test rather than one fixed ohm value:
| Status code | What those instructions say |
|---|---|
| 1082 or 1182 | Isolation error. If the measured isolation value is below the Isolation Error Threshold, the inverter does not feed the grid. The function text names status code 1082 for that trip. The parameter table names status code 1182. The threshold can be set from 0.1 to 10 megohm. |
| 1083 or 1183 | Isolation warning. The function text names status code 1083 when the measured value falls below an adjustable limit. The warning-threshold parameter names status code 1183, and that threshold can also be set from 0.1 to 10 megohm. With the warning function on, the manual says a warning occurs but not a shutdown. |
| 1189 | Displayed continuously when isolation monitoring is set to “Off (with Warning),” which means the monitoring function is deactivated. |
The instructions also say the inverter measures isolation at the DC terminals before each connection, at least once a day, when monitoring is active. State 475 comes from the insulation paper. Status codes 1082 and 1182 are the trip codes in the GEN24, Tauro, and Verto instructions, and 1083 and 1183 are the warning codes in that same document. Match the code to the document for your model. Do not assume a SnapINverter code and a GEN24 code are the same fault.
What the equipment standards cover
UL describes UL 1741 as the standard for inverters, converters, controllers, and interconnection system equipment used with distributed energy resources. The same UL page lists UL 62109 and IEC 62109 as safety standards for power converters used in photovoltaic power systems, and UL 1699B as the standard for photovoltaic DC arc-fault circuit protection. Those titles say what the standards are for. They do not publish a single insulation-resistance trip point, in ohms, for every residential inverter.
NLR’s summary of IEEE Std 1547-2018 says the standard’s purpose is interconnection of distributed energy resources with the grid, including grid support under abnormal conditions. It also says the standard is not a design handbook. The ohms limit that stops your inverter is the limit in that inverter’s manual.
Fronius’s insulation paper says older inverter standards, which it marks as no longer applicable, required insulation resistance of at least 1 kilohm times maximum PV voltage. For a 1,000 V inverter that rule produced 1,000 kilohm, or 1 megohm. The paper then shows why a present-day inverter does not use that single figure for every array. The trip point has to be read from the product, which is why the GEN24 family exposes a 0.1 to 10 megohm setting and why state 475 still requires a qualified electrician.
What to do with the code you wrote down
- Grid events 101 to 103, 202 to 203, 205, or 301 on a Sunny Boy covered by SB30-60TL-21-SG-en-11: the inverter has left the grid because of voltage, impedance, a disconnected grid, or a damaged AC cable. Leave AC conductors alone. If the message remains after the utility is stable, use the manual’s path and contact the grid operator or SMA Service.
- SMA 3501, 3502, 3503, 3601, or 3701: stop. The insulation document assigns the inspection to a qualified person.
- Fronius 475, 1082, 1182, or a repeated 1083 or 1183: stop. State 475 is a ground-fault test for a qualified electrician. Codes 1082 and 1182 mean the inverter is refusing to feed because isolation is below its setting. Codes 1083 and 1183 are the warning pair; with the warning function on, the manual says a warning occurs but not a shutdown.
- Any arc-fault wording on the display: stop and call a qualified person. UL 1699B is the arc-fault protection standard named by UL. The numeric arc code is whatever your model’s manual prints, and this article does not substitute a code from another brand.
- A code that is not in the manual for your model: do not guess from a list written for a different inverter. Contact the manufacturer’s support channel with the model, serial number, and the exact message.
Sources: SMA Sunny Boy 3000TL–6000TL service manual, SMA, Insulation Error in PV Systems, Fronius, DC Insulation Resistance of PV Systems, Fronius GEN24, Tauro, and Verto country-setup instructions, UL inverter and converter certification, NLR highlights of IEEE Std 1547-2018.
Leave a Comment
Your comment will be published after it has been approved. Please send comments that do not contain slang words.