Inverter Isolation Fault, Explained

Inverter Isolation Fault: How to Trace It

An isolation fault means the inverter measured the resistance between the DC conductors and ground, found it below the limit set for that model, and refused to feed the grid. There is no single residential limit of 1 megohm. Fronius documents presets from 34 kilohm to 1,000 kilohm depending on the series, and its GEN24, Tauro, and Verto instructions allow the error threshold to be set anywhere from 0.1 to 10 megohm.

Tracing the fault means testing the array and the DC wiring. SMA and Fronius both assign that work to a qualified person. Do not open the inverter, disconnect DC connectors, pull fuses on a live string, or separate modules. Those steps put you on energized DC conductors. DC arcs do not behave like household AC, and a connector that looks dry can still be part of a live circuit.

What the measurement is

SMA’s technical information “Insulation Error in PV Systems” says its inverters carry a protective device that looks for insulation errors on the DC side and measures insulation resistance before connecting to the utility grid. If the value is below the minimum, the inverter shows an error and does not connect. The low-resistance message is event 3501, with the words “Insulation failure” and “Check generator.” The DC installation’s insulation resistance is or was too low.

Fronius’s country-setup instructions for GEN24, Tauro, and Verto say the inverter performs an isolation measurement at the DC terminals before each connection, at least once a day, when isolation monitoring is on. If the measured value is under the Isolation Error Threshold, grid feed is prevented. The function text says that trip shows status code 1082. The parameter table for the same threshold, which can be set from 0.1 to 10 megohm, says the trip shows status code 1182. A separate warning threshold, also settable from 0.1 to 10 megohm, shows status code 1083 in the function text and status code 1183 in the parameter table. With the warning function on, the manual says a warning occurs but not a shutdown. Status code 1189 means monitoring has been switched to “Off (with Warning),” so that code is a configuration message, not a measured fault.

The inverter is doing a safety test. A trip means the test failed its setting. It does not, by itself, tell you which connector, module, or cable is wet or damaged.

Why the ohm limit changes with the product and the array

Fronius’s June 2026 paper “DC Insulation Resistance of PV Systems” walks through the standards it uses and then publishes its own presets. It identifies IEC 62109-2 as the inverter safety standard for power converters in photovoltaic systems, IEC 63112 for earth-fault protection equipment, and IEC 60364-7-712 for insulation-resistance thresholds that depend on PV array size. For modules, the paper says IEC 61215-2 requires insulation resistance of at least 40 megohm-square-metres. Because that figure is per square metre, a larger array has a lower resistance even when every module meets the module test.

The paper marks an older inverter rule as no longer applicable: insulation resistance not less than 1 kilohm times maximum PV voltage. On a 1,000 V inverter that rule was 1,000 kilohm, which is 1 megohm. Fronius then explains the conflict. Shock-protection rules are aimed at fault current, and the paper says standards in that family require fault current not to exceed 30 milliamps. A large array can measure below 1 megohm and still satisfy the 40 megohm-square-metre module rule. The paper’s own example is a 15 kW array of 30 modules at about 2 square metres each, 60 square metres in total, giving 40 ÷ 60 = 0.67 megohm. Under the old 1 megohm rule the inverter would stay offline and show state 475 even though each module could still meet the area rule. The paper says module resistance is often higher than 40 megohm-square-metres, so this situation is not the usual case, and it is more likely on larger arrays.

Fronius sets many presets tighter than the minimum the paper describes. For inverters up to 15 kW it describes a preset aimed at fault current no higher than 10 milliamps, written as 100 kilohm (1,000 V ÷ 10 mA), and it says the preset may deviate. Above 15 kW the presets are lower, following the direction of the IEC 60364-7-712 table, and still above the minimum the paper cites. Appendix A of that June 2026 paper includes these presets. The paper says values may deviate for specific setups:

Fronius series Preset Device limit
Argeno 36 kilohm 36 to 1,000 kilohm
Tauro (ECO) 34 kilohm 10 to 10,000 kilohm
Verto (Plus) 34 kilohm 34 to 10,000 kilohm
Symo and Primo Gen24 (Plus) 100 kilohm 100 to 10,000 kilohm
Primo 1,000 kilohm 1,000 to 10,000 kilohm
Galvo 600 kilohm 100 to 10,000 kilohm

A Primo preset of 1,000 kilohm and a Gen24 preset of 100 kilohm are both Fronius values. Quoting “1 megohm for most string inverters” erases that table. The GEN24, Tauro, and Verto instructions add a second fact: the error threshold the installer can set runs from 0.1 to 10 megohm, and status code 1082 or 1182, depending on whether you are reading the function text or the parameter table, appears when the measurement is under the value actually configured. One hundred kilohm is 0.1 megohm, the bottom of that range. The number on your screen is the configured threshold, not a universal constant.

UL’s certification page names UL 1741 for inverters and interconnection equipment, and UL 62109 and IEC 62109 for converter safety. NLR’s summary of IEEE Std 1547-2018 describes interconnection requirements, including grid support under abnormal conditions, and says the standard is not a design handbook. Those pages describe certification and interconnection. They are not the source of the ohm table above.

Rain and dew

SMA’s insulation paper says event 3501 can be temporary and is influenced by rain or dew. It also lists storm damage among the conditions that expose a damaged cable or plug, and it says wind can move a conductor with broken insulation onto a grounded part. The usual physical cause it names is defective insulation or a faulty plug on a module or in the DC wiring.

A message that appears after rain and disappears in dry weather still matches the failure mode SMA describes. The paper says these faults are not always easy to detect and that a thorough inspection remains necessary. Drying weather does not finish the repair if a seal or a plug is letting water in. Do not open connectors to wipe them. Call the qualified person the manual names.

Codes that mean “stop”

Code Source Meaning in that document
SMA 3501 Insulation Error in PV Systems Insulation failure. DC insulation resistance is or was too low. The inverter disconnects or will not connect.
SMA 3502 and 3503 Same SMA paper Grouped with 3501 as insulation errors. The paper does not give them a separate homeowner definition.
SMA 3601 and 3701 Same SMA paper Grouped as leakage or residual-current events. Inspection is by a qualified person.
Fronius 475 DC Insulation Resistance paper LOW DC ISOLATION. A qualified electrician must test the system for ground faults.
Fronius 1082 or 1182 GEN24, Tauro, and Verto instructions Measured isolation is below the configured error threshold. No grid feed. The function text uses 1082 and the parameter table uses 1182 for this trip. The warning pair in the same section is 1083 and 1183.

Other brands use other numbers. A code that is not in your model’s manual is not one of the rows above.

What you can do, and what you must leave alone

You can record the code, the words on the display, the model, and the weather at the time. You can leave the system in the state the inverter chose, which is offline, until a qualified installer or electrician has found the circuit. You can tell that person whether the message follows rain.

You cannot safely narrow the fault by pulling strings apart. SMA says the corrective measures in its insulation paper may only be carried out by qualified persons. Fronius says state 475 requires a qualified electrician to test for ground faults. The test they perform, including any insulation test at high voltage and any disconnection of modules, is their work. Lowering a Fronius threshold because an array is large is a decision the paper says must be clarified with the system owner, the authorities, the manufacturers, and the installer. It is not a reset button.

If the inverter shows an insulation or isolation code, the next call is to a qualified solar installer or electrician, with the code in hand. Do not open live DC wiring while you wait.

For the wider, document-specific code overview, see solar inverter error codes by brand and model. The solar inverter topic guide maps the related maintenance and monitoring guides.

Sources: SMA, Insulation Error in PV Systems, Fronius, DC Insulation Resistance of PV Systems, Fronius GEN24, Tauro, and Verto country-setup instructions, UL inverter and converter certification, NLR highlights of IEEE Std 1547-2018.